Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2018, 06:49 AM
  • C 0387_C 0386_07022018_232846.mp4

Date
02/07/2018
W/O
684709
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00142
PipeID
P09851
Time
10:49 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5435
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_684709_TV19054_FEB2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
C 0387
Downstream MH
C 0386
Dir. of Survey
Downstream
Length Surveyed
527.9 ft.
Total Length
527.9 ft.
Structural Index
4
Structural Quick
5L3T
Structural Rating
635
O&M Index
3
O&M Quick
413S
O&M Rating
313
Overall Index
3
Overall Quick
Overall Rating
948
Pipe schematic from manhole C 0387 to C 0386
MH: C 0387MH: C 0386downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03870 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.9 ft. MGO - General Observation - MAG COAT4.7 ft. IW - Infiltration Weeper, from 07 to 09 o'clock, within 8 inches of joint: YES4.7 ft. IR - Infiltration Runner, from 02 to 04 o'clock, within 8 inches of joint: YES8.3 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES12.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish12.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start47.8 ft. IW - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES123.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"320.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355.5 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES437.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"500.5 ft. IS - Infiltration Stain, from 02 to 04 o'clock, within 8 inches of joint: NO503.5 ft. IS - Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: NO518.8 ft. IW - Infiltration Weeper, from 08 to 11 o'clock, within 8 inches of joint: NO527.9 ft. AMH - Downstream Manhole, Survey Ends - C 0386527.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish527.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (11)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Weeper, from 07 to 09 o'clock, within 8 inches of joint: YES

    4.7 ft. - Infiltration Weeper, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, from 02 to 04 o'clock, within 8 inches of joint: YES

    4.7 ft. - Infiltration Runner, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES

    8.3 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES

    47.8 ft. - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES

    355.5 ft. - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 02 to 04 o'clock, within 8 inches of joint: NO

    500.5 ft. - Infiltration Stain, from 02 to 04 o'clock, within 8 inches of joint: NO

  • Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: NO

    503.5 ft. - Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: NO

  • Infiltration Weeper, from 08 to 11 o'clock, within 8 inches of joint: NO

    518.8 ft. - Infiltration Weeper, from 08 to 11 o'clock, within 8 inches of joint: NO

Observations (23)

DistanceCodeObservation
8.3IS
527.9AMHC 0386
0AMHC 0387
12.1SRV
500.5IS
4.7IW
2.2SRV
2.1SAP
527.9DSZ
25.9DSZ
518.8IW
437.6TF
12.5SRV
0MWM
320.7SRV
4.7IR
503.5IS
0MWL
123.5TF
355.5ID
47.8IW
2.9MGOMAG COAT
527.9SAP

Properties (5)

additional_info
SC347073
custom_field_two
2
customer
LACSD
datetime
2018-02-07T22:49:37-08:00
year_laid
26643