Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2018, 08:45 AM
  • 02 0132_02 0131_2212018_012038.mp4

Date
02/21/2018
W/O
0689513
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02433
Time
12:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0746
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20180221MDM_DOWNEY_BELLFLOWER_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
02 0132
Downstream MH
02 0131
Dir. of Survey
Downstream
Length Surveyed
298.5 ft.
Total Length
298.5 ft.
Structural Index
4
Structural Quick
5439
Structural Rating
47
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
49
Pipe schematic from manhole 02 0132 to 02 0131
MH: 02 0132MH: 02 0131downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM2 ft. MGO - General Observation - 3 MISSING TILES AT 12:002 ft. SAP - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO3 ft. MGO - General Observation - 100% IN PLACE TILES START 7:00 TO 5:0022.2 ft. MGO - General Observation - 40% MISSING TILES22.2 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG30.4 ft. MGO - General Observation - 1 MISSING TILE 12:0037.3 ft. MGO - General Observation - 30% MISSING TILES 10:00 TO 2:0040.3 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG45 ft. MGO - General Observation - 5% MISSING TILES 12:0049.4 ft. MGO - General Observation - 15% MISING TILES 11:00 TO 1:0053.5 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG60.9 ft. MGO - General Observation - 5% MISSING TILES71.3 ft. MGO - General Observation - 20% MISSING TILES 11:00 TO 1:0073.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR POSSIBLE79.2 ft. SAP - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG85.9 ft. MGO - General Observation - 15% MISSING TILES 12:0097.8 ft. MGO - General Observation - 1 MISSING TILE 12:00109.6 ft. MGO - General Observation - 3 MISSING TILES 12:00113.7 ft. MGO - General Observation - 15% MISSING TILES 12:00123.9 ft. MGO - General Observation - MISSING TILES 5% START144.3 ft. MGO - General Observation - 10% MISSING TILES169.5 ft. MGO - General Observation - 40% MISSING TILES 11:00 TO 2:00173 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG177.4 ft. MGO - General Observation - 30% MISSING TILES START180.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, - LONG & CIRCUM REBAR182.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - TILES190.3 ft. MGO - General Observation - 30% MISSING TILES FINISH192.6 ft. MGO - General Observation - 5% MISSING TILES START210 ft. MGO - General Observation - 20% MISSING TILES218.3 ft. MGO - General Observation - 30% MISSING TILES220.4 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG262.7 ft. MGO - General Observation - 50% MISSING TILES262.7 ft. SAP - Surface Aggregate Projecting, from 10 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG267.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM281.7 ft. MGO - General Observation - 50% MISSING TILES START281.7 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG285.5 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR298.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN298.2 ft. MGO - General Observation - 50 5 MISSING TILES FINISH298.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR298.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR298.2 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG298.5 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (25)

  • Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: NO

  • General Observation - 100% IN PLACE TILES START 7:00 TO 5:00

    3 ft. - General Observation - 100% IN PLACE TILES START 7:00 TO 5:00

  • General Observation - 40% MISSING TILES

    22.2 ft. - General Observation - 40% MISSING TILES

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    22.2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 30% MISSING TILES 10:00 TO 2:00

    37.3 ft. - General Observation - 30% MISSING TILES 10:00 TO 2:00

  • General Observation - 5% MISSING TILES 12:00

    45 ft. - General Observation - 5% MISSING TILES 12:00

  • General Observation - 15% MISING TILES 11:00 TO 1:00

    49.4 ft. - General Observation - 15% MISING TILES 11:00 TO 1:00

  • General Observation - 20% MISSING TILES 11:00 TO 1:00

    71.3 ft. - General Observation - 20% MISSING TILES 11:00 TO 1:00

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR POSSIBLE

    73.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR POSSIBLE

  • General Observation - 15% MISSING TILES 12:00

    85.9 ft. - General Observation - 15% MISSING TILES 12:00

  • General Observation - 15% MISSING TILES 12:00

    113.7 ft. - General Observation - 15% MISSING TILES 12:00

  • General Observation - MISSING TILES 5% START

    123.9 ft. - General Observation - MISSING TILES 5% START

  • General Observation - 10% MISSING TILES

    144.3 ft. - General Observation - 10% MISSING TILES

  • General Observation - 40% MISSING TILES 11:00 TO  2:00

    169.5 ft. - General Observation - 40% MISSING TILES 11:00 TO 2:00

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    173 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 30% MISSING TILES START

    177.4 ft. - General Observation - 30% MISSING TILES START

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO,  - LONG & CIRCUM REBAR

    180.2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, - LONG & CIRCUM REBAR

  • General Observation - 5% MISSING TILES START

    192.6 ft. - General Observation - 5% MISSING TILES START

  • General Observation - 20% MISSING TILES

    210 ft. - General Observation - 20% MISSING TILES

  • General Observation - 30% MISSING TILES

    218.3 ft. - General Observation - 30% MISSING TILES

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    220.4 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 50% MISSING TILES

    262.7 ft. - General Observation - 50% MISSING TILES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

    267.1 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

  • General Observation - 50% MISSING TILES START

    281.7 ft. - General Observation - 50% MISSING TILES START

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    285.5 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

Observations (46)

DistanceCodeObservation
22.2MGO40% MISSING TILES
173SAPSEVERE AGG
180.2SRVLONG & CIRCUM REBAR
262.7MGO50% MISSING TILES
97.8MGO1 MISSING TILE 12:00
22.2SAPSEVERE AGG
298.2MGOConn. @ Mh, 3 O' Clock. OPEN
281.7MGO50% MISSING TILES START
37.3MGO30% MISSING TILES 10:00 TO 2:00
73.7SRVLONG & CIRCUM REBAR POSSIBLE
0MWL
79.2SAPSEVERE AGG
49.4MGO15% MISING TILES 11:00 TO 1:00
298.2MGO50 5 MISSING TILES FINISH
267.1SRVCIRCUM
71.3MGO20% MISSING TILES 11:00 TO 1:00
190.3MGO30% MISSING TILES FINISH
3MGO100% IN PLACE TILES START 7:00 TO 5:00
45MGO5% MISSING TILES 12:00
2MGO3 MISSING TILES AT 12:00
169.5MGO40% MISSING TILES 11:00 TO 2:00
182.9DSZTILES
123.9MGOMISSING TILES 5% START
262.7SAPSEVERE AGG
285.5SRVCIRCUM REBAR
109.6MGO3 MISSING TILES 12:00
60.9MGO5% MISSING TILES
298.2SRVCIRCUM REBAR
298.2SRVCIRCUM REBAR
220.4SAPSEVERE AGG
192.6MGO5% MISSING TILES START
177.4MGO30% MISSING TILES START
2SAP
281.7SAPSEVERE AGG
218.3MGO30% MISSING TILES
40.3SAVSEVERE AGG
113.7MGO15% MISSING TILES 12:00
210MGO20% MISSING TILES
144.3MGO10% MISSING TILES
298.5AMH2:05AM
85.9MGO15% MISSING TILES 12:00
298.2SAPSEVERE AGG
30.4MGO1 MISSING TILE 12:00
0MWM
53.5SAVSEVERE AGG
0AMH12:55AM

Properties (4)

custom_field_three
LONG & CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2018-02-21T00:45:11-08:00