Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2016, 11:26 AM
  • A 0307_A 0306 _20062016_043029.mp4

Date
06/20/2016
W/O
574385
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00325
PipeID
P08217
Time
4:26 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3535
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_574385_TV15129_JUNE2016
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
A 0306
Downstream MH
A 0307
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole A 0306 to A 0307
MH: A 0306MH: A 0307upstream0 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.2 ft. MWL - Water Level, 35 %of cross sectional area2 ft. AMH - Downstream Manhole, Survey Begins - A 03062 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (4)

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

Observations (7)

DistanceCodeObservation
0MWL
0AMHA 0306
2SSS
2DAGS
0MWM
2SAP
2MSAVIEW OF UPLEG OF D/S SIPHON.

Properties (5)

additional_info
SC305769
custom_field_two
3
customer
LACSD
datetime
2016-06-20T04:26:00-07:00
year_laid
28972