Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2018, 08:38 AM
  • 08 0365_08 0364_2172018_030559.mp4

Date
02/17/2018
W/O
0690350
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00003
PipeID
P00417
Time
12:38 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0743
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
Carson
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Capital Improvement Program Assesment
Project
20180217VMR_DAVIDSON_CITY_TRUNK_SECTS_123
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
08 0365
Downstream MH
08 0364
Dir. of Survey
Downstream
Length Surveyed
141.6 ft.
Total Length
141.6 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 08 0365 to 08 0364
MH: 08 0365MH: 08 0364downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03:05 AM0.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"0.9 ft. SAVC - Surface Aggregate Visible Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - Mag Coat29.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open65.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"96 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"98.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES110.2 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES120.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"125.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES137.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES139.2 ft. SAVC - Surface Aggregate Visible Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - Mag Coat141.6 ft. AMH - Downstream Manhole, Survey Ends - 03:19 AM

Observations (15)

DistanceCodeObservation
141.6AMH03:19 AM
96TFC
137.4CL
120.3TF
0MWL
0.9TFA
0MWM
29.3TFOpen
125.6CL
0.9SAVCMag Coat
110.2CC
0AMH03:05 AM
98.3CL
139.2SAVCMag Coat
65.5TFC

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-02-17T00:38:42-08:00