Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2018, 08:37 AM
  • 08 0366_08 0365_2172018_005556.mp4

Date
02/17/2018
W/O
0690350
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00003
PipeID
P00418
Time
12:37 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0743
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
Carson
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Capital Improvement Program Assesment
Project
20180217VMR_DAVIDSON_CITY_TRUNK_SECTS_123
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
08 0365
Downstream MH
08 0366
Dir. of Survey
Upstream
Length Surveyed
141.4 ft.
Total Length
141.4 ft.
Structural Index
2
Structural Quick
3121
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 08 0365 to 08 0366
MH: 08 0365MH: 08 0366upstream0 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"0 ft. AMH - Upstream Manhole, Survey Ends - 12:40 AM2.2 ft. SAVC - Surface Aggregate Visible Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish14.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4" - Capped43.9 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES48 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"48.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES74.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open90.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"92.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Capped140.4 ft. SAVC - Surface Aggregate Visible Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - Mag Coat141.4 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"141.4 ft. MWM - Water Mark, 40 %of cross sectional area141.4 ft. AMH - Downstream Manhole, Survey Begins - 12:05 AM141.4 ft. MWL - Water Level, 25 %of cross sectional area

Observations (15)

DistanceCodeObservation
93.4TFA
0TFA
66.8TFOpen
48.6TFCCapped
141.4TFC
0MWM
127.2TFCCapped
92.6CL
0AMH12:05 AM
1SAVCMag Coat
141.4AMH12:40 AM
139.2SAVC
97.5CC
0MWL
50.6TFC

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-02-17T00:37:32-08:00