Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2018, 01:17 PM
  • 08 0370_08 0369_2162018_052301.mp4

Date
02/16/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00003
PipeID
P00422
Time
5:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0741
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
20180216MDM_DAVIDSON_CITY_TRUNK_SECTS_1_2_3
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
08 0369
Downstream MH
08 0370
Dir. of Survey
Upstream
Length Surveyed
141.8 ft.
Total Length
141.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 08 0369 to 08 0370
MH: 08 0369MH: 08 0370upstream0 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM0.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active7.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped34.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped53 ft. RFB - Roots Fine Barrell, from 10 to 02 o'clock, within 8 inches of joint: YES - 2%62.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped67.2 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SLIGHT86 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active139.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG141.8 ft. MWM - Water Mark, 40 %of cross sectional area141.8 ft. AMH - Downstream Manhole, Survey Begins - 5:25AM141.8 ft. MWL - Water Level, 10 %of cross sectional area141.8 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

Observations (14)

DistanceCodeObservation
0MWM
141.4SAPSEVERE AGG
2SAPSEVERE AGG
55.8TFActive
74.6FCSLIGHT
0AMH5:25AM
133.9TFCCapped
141.4MGOConn. @ Mh, 3 O' Clock. Active
107.2TFCCapped
141.8AMH5:50AM
0MWL
0MGOConn. @ Mh, 3 O' Clock. Active
88.8RFB2%
79.5TFCCapped

Properties (5)

additional_info
REVERSE INSPECTION
custom_field_three
PROJECTIN SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2018-02-16T05:17:08-08:00