Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2016, 08:52 AM
  • 14 0118_14 0117 _08242016_015309.mp4

Date
08/24/2016
W/O
579900
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P18148
Time
1:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3644
Sewer Name
14 DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_579900_TV14007_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0118
Downstream MH
14 0117
Dir. of Survey
Downstream
Length Surveyed
420.6 ft.
Total Length
420.6 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
155
O&M Index
2
O&M Quick
4131
O&M Rating
339
Overall Index
2
Overall Quick
Overall Rating
494
Pipe schematic from manhole 14 0118 to 14 0117
MH: 14 0118MH: 14 0117downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 01180 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start28 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"42.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES45.4 ft. TBD - Tap Break-In Defective, at 09 o'clock, -, , within 8 inches of joint: NO, 6" - ROOTS61.4 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"61.4 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"134.9 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES149.9 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"150.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES157.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"174.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start179.9 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"181.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"269.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"276.6 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"298.3 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"300.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"387 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"390.5 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"417.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish419.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish419.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish420.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0117

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    42.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Defective, at 09 o'clock, -,  , within 8 inches of joint: NO, 6" - ROOTS

    45.4 ft. - Tap Break-In Defective, at 09 o'clock, -, , within 8 inches of joint: NO, 6" - ROOTS

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    134.9 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    150.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    174.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
0AMH14 0118
45.4TBDROOTS
300.9TBA
157.9TBA
181.9TBA
150.6CM
269.1TBA
2DAGS
419.5DAGS
134.9CS
417.6CM
61.4TBA
28TBA
419.5DAE
174.2CM
276.6TBA
2.4DAE
179.9TBA
0MWL
387TBA
42.3CM
390.5TBA
0MWM
420.6AMH14 0117
61.4TBA
149.9TBA
298.3TBA

Properties (4)

additional_info
SC306081
custom_field_two
3
customer
LACSD
datetime
2016-08-24T01:52:25-07:00