Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2018, 11:01 AM
  • 03 0476_03 0475_2162018_032129.mp4

Date
02/16/2018
W/O
PENDING
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00401
PipeID
P05196
Time
3:01 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7634
Sewer Name
03 PUMP DISTRICT #5 CONNECTION TRUNK
City
LONG BEACH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
22
Purpose
Routine Assessment
Project
20180216DF_PUMP_DISTRICT_5_CONN_TR
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
03 0476
Downstream MH
03 0475
Dir. of Survey
Downstream
Length Surveyed
256.4 ft.
Total Length
256.4 ft.
Structural Index
3
Structural Quick
5642
Structural Rating
70
O&M Index
3
O&M Quick
4231
O&M Rating
17
Overall Index
3
Overall Quick
Overall Rating
87
Pipe schematic from manhole 03 0476 to 03 0475
MH: 03 0476MH: 03 0475downstream0 ft. AMH - Downstream Manhole, Survey Begins - 3:13 AM0.1 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MGP - General Photograph0.1 ft. MWM - Water Mark, 15 %of cross sectional area5 ft. JOL - Joint Offset Large12.1 ft. B - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES12.1 ft. JOM - Joint Offset Medium24.8 ft. JOM - Joint Offset Medium30.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES33.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock, , within 8 inches of joint: YES37 ft. CC - Crack Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES37 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start39.8 ft. MGP - General Photograph39.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES42.8 ft. B - Broken, from 02 to 03 o'clock, within 8 inches of joint: YES42.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES47.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.8 ft. FS - Fracture Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES54.8 ft. B - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES58 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES118.6 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish151.9 ft. B - Broken, from 09 to 02 o'clock, within 8 inches of joint: YES151.9 ft. ID - Infiltration Dripper, at 09 o'clock, within 8 inches of joint: YES164.1 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES182 ft. B - Broken, from 09 to 12 o'clock, within 8 inches of joint: YES203.2 ft. B - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES203.2 ft. IR - Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES209.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start224.3 ft. JSM - Joint Separated Medium236.4 ft. FS - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES, Start240.9 ft. FS - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES, Finish242.6 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - INSIDE THE JOINT242.6 ft. IR - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES242.6 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES254.8 ft. B - Broken, from 02 to 03 o'clock, within 8 inches of joint: YES255.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish256.4 ft. AMH - Downstream Manhole, Survey Ends - 4:23 AM256.4 ft. MGO - General Observation - Grease Throughout The Reach (5%)

Observation photos (28)

  • Joint Offset Large

    5 ft. - Joint Offset Large

  • Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

    12.1 ft. - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    24.8 ft. - Joint Offset Medium

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    30.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock,  , within 8 inches of joint: YES

    33.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock, , within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES

    37 ft. - Crack Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    37 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph

    39.8 ft. - General Photograph

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    39.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Broken, from 02 to 03 o'clock, within 8 inches of joint: YES

    42.8 ft. - Broken, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    42.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    47.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    51.8 ft. - Fracture Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

    54.8 ft. - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    58 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Broken, from 09 to 02 o'clock, within 8 inches of joint: YES

    151.9 ft. - Broken, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 09 o'clock, within 8 inches of joint: YES

    151.9 ft. - Infiltration Dripper, at 09 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    164.1 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 09 to 12 o'clock, within 8 inches of joint: YES

    182 ft. - Broken, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

    203.2 ft. - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES

    203.2 ft. - Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    209.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Joint Separated Medium

    224.3 ft. - Joint Separated Medium

  • Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES, Start

    236.4 ft. - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 12 o'clock, within 8 inches of joint: YES - INSIDE THE JOINT

    242.6 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - INSIDE THE JOINT

  • Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

    242.6 ft. - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

    242.6 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Broken, from 02 to 03 o'clock, within 8 inches of joint: YES

    254.8 ft. - Broken, from 02 to 03 o'clock, within 8 inches of joint: YES

Observations (39)

DistanceCodeObservation
58FL
30.4CL
242.6HINSIDE THE JOINT
255.7CM
254.8B
0.1MWL
118.6DAE
209.4DAE
37CC
24.8JOM
242.6IR
39.8MGP
0.1MGP
5JOL
54.8B
47.1CM
33.7DAE
0AMH3:13 AM
12.1B
236.4FS
39.8CL
42.8B
151.9B
203.2B
37DAE
42.8CM
51.8FS
242.6FS
12.1JOM
0.1MWM
182B
164.1B
203.2IR
240.9FS
256.4AMH4:23 AM
255.7DAE
151.9ID
224.3JSM
256.4MGOGrease Throughout The Reach (5%)

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-02-16T03:01:09-08:00