Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2018, 08:57 AM
  • 15 0744_15 0743 _31012018_011333.mp4

Date
01/31/2018
W/O
684713
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00593
PipeID
P12943
Time
12:57 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4860
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_684713_TV15146_FEB2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0744
Downstream MH
15 0743
Dir. of Survey
Downstream
Length Surveyed
346.1 ft.
Total Length
346.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0744 to 15 0743
MH: 15 0744MH: 15 0743downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07443.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start7.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"83.9 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 6"134.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"137.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"231.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"234.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"298.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"309 ft. DAZ - Deposits Attached Other, 10 %of cross sectional area, at 07 o'clock, , within 8 inches of joint: YES337.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"346.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0743346.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    3.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Deposits Attached Other, 10 %of cross sectional area, at 07 o'clock,  , within 8 inches of joint: YES

    309 ft. - Deposits Attached Other, 10 %of cross sectional area, at 07 o'clock, , within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
298.1TF
134.9TF
137.9TF
231.5TF
346.1AMH15 0743
309DAZ
7.9TF
0MWM
337.5TF
3.2SAV
40.9TF
83.9TB
234.2TB
346.1SAV
0MWL
0AMH15 0744

Properties (4)

additional_info
SC346884
custom_field_two
4
customer
LACSD
datetime
2018-01-31T00:57:34-08:00