Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2018, 07:32 AM
  • J 0191_J 0190 _31012018_235420.mp4

Date
01/31/2018
W/O
684818
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00055
PipeID
P11430
Time
11:32 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5430
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
SAN PEDRO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47A
Purpose
Routine Assessment
Project
WO_684818_TV05311_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
J 0191
Downstream MH
J 0190
Dir. of Survey
Downstream
Length Surveyed
590.7 ft.
Total Length
590.7 ft.
Structural Index
3
Structural Quick
3G24
Structural Rating
122
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
122
Pipe schematic from manhole J 0191 to J 0190
MH: J 0191MH: J 0190downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 01910 ft. MWM - Water Mark, 20 %of cross sectional area55.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES346.2 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES371.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES376.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start432 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish443.6 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES448.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start584.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish590.7 ft. AMH - Downstream Manhole, Survey Ends - J 0190

Observation photos (6)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    55.5 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    346.2 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    371.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    376.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    443.6 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    448.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
346.2CS
0MWL
0AMHJ 0191
432CM
376.8CM
55.5CL
590.7AMHJ 0190
448.6CM
443.6CL
0MWM
371.2CL
584.8CM

Properties (4)

additional_info
SC347065
custom_field_two
3
customer
LACSD
datetime
2018-01-31T23:32:35-08:00