Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2016, 07:16 AM
  • 18 0517_18 0516 _01072016_001647.mp4

Date
07/01/2016
W/O
579947
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00705
PipeID
P14371
Time
12:16 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3551
Sewer Name
18 SOUTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
10
Purpose
Routine Assessment
Project
WO_579947_TV18055_JULY2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0516
Downstream MH
18 0517
Dir. of Survey
Upstream
Length Surveyed
327.8 ft.
Total Length
327.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2L1C
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
152
Pipe schematic from manhole 18 0516 to 18 0517
MH: 18 0516MH: 18 0517upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 05170 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish78.5 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Finish177.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES177.7 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start325.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start327.8 ft. MWL - Water Level, 15 %of cross sectional area327.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE327.8 ft. MWM - Water Mark, 25 %of cross sectional area327.8 ft. AMH - Downstream Manhole, Survey Begins - 18 0516

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    150.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start

    150.1 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start

  • General Observation - COCKROACHES IN MANHOLE

    327.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0MWL
327.8AMH18 0517
327.8MGOCOCKROACHES IN MANHOLE
150.1CL
249.3RFJ
0MGOCOCKROACHES IN MANHOLE
325.9DAE
2DAE
0MWM
150.1RFJ
0AMH18 0516

Properties (5)

additional_info
SC305780
custom_field_two
4
customer
LACSD
datetime
2016-07-01T00:16:02-07:00
sewer_category
Gravity