- Date
- 06/30/2016
- W/O
- 579947
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00705
- PipeID
- P14374
- Time
- 3:08 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3550
- Sewer Name
- 18 SOUTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- WO_579947_TV18055_JULY2016
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 18 0519
- Downstream MH
- 18 0520
- Dir. of Survey
- Upstream
- Length Surveyed
- 352.2 ft.
- Total Length
- 352.2 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 2
- O&M Quick
- 2[00
- O&M Rating
- 280
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 283
Pipe schematic from manhole 18 0519 to 18 0520 Observation photos (4)

2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

45.9 ft. - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

352.2 ft. - General Observation - COCKROACHES IN MANHOLE