Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2016, 09:33 AM
  • 18 0510_18 0509 _01072016_023330.mp4

Date
07/01/2016
W/O
579947
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00705
PipeID
P14364
Time
2:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3551
Sewer Name
18 SOUTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
10
Purpose
Routine Assessment
Project
WO_579947_TV18055_JULY2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0510
Downstream MH
18 0509
Dir. of Survey
Downstream
Length Surveyed
304.1 ft.
Total Length
304.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3J2K
O&M Rating
282
Overall Index
2
Overall Quick
Overall Rating
282
Pipe schematic from manhole 18 0510 to 18 0509
MH: 18 0510MH: 18 0509downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 05100 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 10 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start34 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start304.1 ft. MSA - Survey Abandoned - DUE TO DEBRIS/DEPOSITS304.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish304.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - DUE TO DEBRIS/DEPOSITS

    304.1 ft. - Survey Abandoned - DUE TO DEBRIS/DEPOSITS

Observations (10)

DistanceCodeObservation
34DSZ
0MWL
0MWM
0AMH18 0510
304.1MSADUE TO DEBRIS/DEPOSITS
304.1DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOACTIVE CONNECTION AT MH 10 O'CLOCK
304.1DSZ
2DAGS

Properties (5)

additional_info
SC305780
custom_field_two
5
customer
LACSD
datetime
2016-07-01T02:33:12-07:00
sewer_category
Gravity