Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 5, 2016, 09:19 AM
  • 18 0508_18 0507 _05072016_022147.mp4

Date
07/05/2016
W/O
579947
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00705
PipeID
P14362
Time
2:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3552
Sewer Name
18 SOUTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
10
Purpose
Routine Assessment
Project
WO_579947_TV18055_JULY2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0508
Downstream MH
18 0507
Dir. of Survey
Downstream
Length Surveyed
589.5 ft.
Total Length
589.5 ft.
Structural Index
3
Structural Quick
3S21
Structural Rating
305
O&M Index
2
O&M Quick
2n00
O&M Rating
468
Overall Index
2
Overall Quick
Overall Rating
773
Pipe schematic from manhole 18 0508 to 18 0507
MH: 18 0508MH: 18 0507downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 05080 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start16.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES81.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start587.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish587.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish587.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish589.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0507589.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE589.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    16.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    81.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    589.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
589.5AMH18 0507
587.7DAE
2DAGS
587.7DAGS
16.3CL
589.5MGOCOCKROACHES IN MANHOLE
0AMH18 0508
587.7CM
589.5MGOCONNECTION AT MH 9 O'CLOCK
2DAE
81.1CM
0MWM
0MWL

Properties (5)

additional_info
SC305781
custom_field_two
4
customer
LACSD
datetime
2016-07-05T02:19:16-07:00
sewer_category
Gravity