Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2015, 09:45 AM
  • 18 0674_18 0673_29092015_024712.mp4

Date
09/29/2015
W/O
521099
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00696
PipeID
P14523
Time
2:45 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2691
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_521099_TV18169_AUG2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 0674
Downstream MH
18 0673
Dir. of Survey
Downstream
Length Surveyed
128.7 ft.
Total Length
128.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
412D
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
60
Pipe schematic from manhole 18 0674 to 18 0673
MH: 18 0674MH: 18 0673downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06730 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start52.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES74.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"92.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES127.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Finish128.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0673128.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    52.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    92.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0MWM
2DAE
92.4CM
0AMH18 0673
0MWL
74.3TFC
127.8DAE
128.7AMH18 0673
128.7MGOACTIVE CONNECTION AT MH 12 O'CLOCK
52.8CM

Properties (5)

additional_info
SC203914
custom_field_two
3
customer
LACSD
datetime
2015-09-29T02:45:55-07:00
sewer_category
GRAVITY