Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2015, 09:02 AM
  • 18 0678_18 0677_29092015_020435.mp4

Date
09/29/2015
W/O
521099
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00696
PipeID
P14527
Time
2:02 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2691
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_521099_TV18169_AUG2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 0678
Downstream MH
18 0677
Dir. of Survey
Downstream
Length Surveyed
194.8 ft.
Total Length
194.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G11
O&M Rating
77
Overall Index
2
Overall Quick
Overall Rating
77
Pipe schematic from manhole 18 0678 to 18 0677
MH: 18 0678MH: 18 0677downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06780 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 04 to 04 o'clock, , within 8 inches of joint: YES, Start14.8 ft. RFC - Roots Fine Connection, at 10 o'clock, within 8 inches of joint: YES14.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"18.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 04 to 04 o'clock, , within 8 inches of joint: YES, Finish194.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0677

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 04 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 04 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Connection, at 10 o'clock, within 8 inches of joint: YES

    14.8 ft. - Roots Fine Connection, at 10 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    14.8 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
14.8RFC
2DAE
0MWL
14.8TBA
192.2DAE
99.6TF
18.9TB
0AMH18 0678
194.8AMH18 0677
0MWM

Properties (5)

additional_info
SC203914
custom_field_two
4
customer
LACSD
datetime
2015-09-29T02:02:56-07:00
sewer_category
GRAVITY