Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2015, 09:16 AM
  • 18 0658_18 0657_02092015_021703.mp4

Date
09/02/2015
W/O
521021
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00696
PipeID
P14507
Time
2:16 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2671
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_521021_TV18081_AUG2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
18 0658
Downstream MH
18 0657
Dir. of Survey
Downstream
Length Surveyed
300.6 ft.
Total Length
300.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 18 0658 to 18 0657
MH: 18 0658MH: 18 0657downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06582 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start8.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"13.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Start157 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Finish205.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES210.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish299.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish300.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0657

Observation photos (1)

  • Repair Localized Liner, within 8 inches of joint: YES, Start

    132.6 ft. - Repair Localized Liner, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MWL
299.5DAGS
2DAGS
2DAE
0MWM
8.6TF
205.5TFC
300.6AMH18 0657
157RPL
299.5DAE
210.3CL
132.6RPL
108.7TFA
210.3TFC
0AMH18 0658
104.3TFC
13.4TFC

Properties (5)

additional_info
SC202943
custom_field_two
3
customer
LACSD
datetime
2015-09-02T02:16:41-07:00
sewer_category