Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 12, 2018, 09:57 AM
  • Section#11_J 0200_J 0198__2122018__G6958.mp4

Date
02/12/2018
W/O
0688894
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11444
Time
1:57 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6958
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
48
Purpose
Capital Improvement Program Assesment
Project
20180210MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0200
Downstream MH
J 0198
Dir. of Survey
Downstream
Length Surveyed
17.7 ft.
Total Length
17.7 ft.
Structural Index
2
Structural Quick
3223
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole J 0200 to J 0198
MH: J 0200MH: J 0198downstream0 ft. MGO - General Observation - MH CONN 3:00 STOPLOG IN PLACE- OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE4.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC8.6 ft. MGO - General Observation - MAG COAT 30% START 8:00 TO 4:0014 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC17.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE17.3 ft. MGO - General Observation - MH CONN 3:00 ACTIVE17.3 ft. MGO - General Observation - MAG COAT 30% FINISH17.7 ft. AMH - Downstream Manhole, Survey Ends - 4:20AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    4.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 30% START 8:00 TO 4:00

    8.6 ft. - General Observation - MAG COAT 30% START 8:00 TO 4:00

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    14 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

Observations (10)

DistanceCodeObservation
17.3SSSBLISTERING PEELING CONCRETE
17.7AMH4:20AM
0MGOMH CONN 3:00 STOPLOG IN PLACE- OPEN
4.5SAVSEVERE AGG SPORATIC
17.3MGOMH CONN 3:00 ACTIVE
8.6MGOMAG COAT 30% START 8:00 TO 4:00
17.3MGOMAG COAT 30% FINISH
0AMH4:10AM
14SAVSEVERE AGG SPORATIC
2SSSBLISTERING PEELING CONCRETE

Properties (4)

custom_field_three
SEVERE AGG SPORATIC
custom_field_two
3
customer
LACSD
datetime
2018-02-12T01:57:12-08:00