Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2018, 09:31 AM
  • Section#2_J 0215_J 0214__2102018__G6956.mp4

Date
02/10/2018
W/O
0688897
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11459
Time
1:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6956
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
48
Purpose
Capital Improvement Program Assesment
Project
20180210MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0215
Downstream MH
J 0214
Dir. of Survey
Downstream
Length Surveyed
433.6 ft.
Total Length
433.6 ft.
Structural Index
2
Structural Quick
2Q00
Structural Rating
176
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
176
Pipe schematic from manhole J 0215 to J 0214
MH: J 0215MH: J 0214downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:30AM2 ft. MGO - General Observation - MAG COAT 75% START 8:0 TO 4:004 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE47.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE83.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE433.1 ft. MGO - General Observation - MAG COAT 70% FINISH433.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELIONG CONCRETE433.6 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observation photos (4)

  • General Observation - MAG COAT 75% START 8:0 TO 4:00

    2 ft. - General Observation - MAG COAT 75% START 8:0 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    47.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

    83.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

Observations (10)

DistanceCodeObservation
4SSSBLISTERING PEELING CONCRETE
47.4SSSBLISTERING CONCRETE
433.6AMH3:05AM
0MWM
0MWL
0AMH2:30AM
2MGOMAG COAT 75% START 8:0 TO 4:00
83.9SSSBLISTERING CONCRETE
433.1MGOMAG COAT 70% FINISH
433.1SSSBLISTERING PEELIONG CONCRETE

Properties (4)

custom_field_three
BLISTERING PEELING CONCRETE
custom_field_two
3
customer
LACSD
datetime
2018-02-10T01:31:27-08:00