Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2018, 06:41 PM
  • Section#2_18 0998_18 0997__222018__G6944.mp4

Date
02/02/2018
W/O
0687662
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00677
PipeID
P14852
Time
10:41 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6944
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20180202DF_LA_HABRA_HEIGHTS_TR_SEC_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 0998
Downstream MH
18 0997
Dir. of Survey
Downstream
Length Surveyed
233.2 ft.
Total Length
233.2 ft.
Structural Index
2
Structural Quick
2H11
Structural Rating
93
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
97
Pipe schematic from manhole 18 0998 to 18 0997
MH: 18 0998MH: 18 0997downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:43 AM0 ft. MGO - General Observation - STOPLOG DOWN @ 3 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.6 ft. MGP - General Photograph52.3 ft. MGP - General Photograph93.1 ft. JOM - Joint Offset Medium, .5"98.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4", 4"102.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4", 4"108.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start115.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish200.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"203 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"230.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish230.6 ft. MGO - General Observation - CHIPPING FROM 10 TO 2 O'CLOCK233.2 ft. AMH - Downstream Manhole, Survey Ends - 11:15 AM

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    23.6 ft. - General Photograph

  • General Photograph

    52.3 ft. - General Photograph

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    108.3 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - CHIPPING FROM 10 TO 2 O'CLOCK

    230.6 ft. - General Observation - CHIPPING FROM 10 TO 2 O'CLOCK

Observations (17)

DistanceCodeObservation
203TFC
98.8TFC
108.3DAGS
0MWL
0AMH10:43 AM
230.1SSS
233.2AMH11:15 AM
2SSS
115.9DAGS
0MGOSTOPLOG DOWN @ 3 O'CLOCK
52.3MGP
230.6MGOCHIPPING FROM 10 TO 2 O'CLOCK
0MWM
200.4TFC
93.1JOM
102.1TFC
23.6MGP

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-02-02T10:41:54-08:00