Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2018, 09:32 AM
  • 05 2232_05 2231 _01042018_013451.mp4

Date
01/04/2018
W/O
679437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00429
PipeID
P07356
Time
1:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5365
Sewer Name
05 COLDEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_679437_TV05094_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 2232
Downstream MH
05 2231
Dir. of Survey
Downstream
Length Surveyed
607.5 ft.
Total Length
607.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 05 2232 to 05 2231
MH: 05 2232MH: 05 2231downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 22320 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area50.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"370.6 ft. CS - Crack Spiral, from 09 to 02 o'clock, within 8 inches of joint: YES607.5 ft. AMH - Downstream Manhole, Survey Ends - 05 2231607.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Observation photos (1)

  • Crack Spiral, from 09 to 02 o'clock, within 8 inches of joint: YES

    370.6 ft. - Crack Spiral, from 09 to 02 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0AMH05 2232
607.5AMH05 2231
0MWM
370.6CS
50.9TF
0MWL
607.5MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Properties (6)

additional_info
SC346442
custom_field_two
3
customer
LACSD
datetime
2018-01-04T01:32:36-08:00
sewer_category
Gravity
year_laid
28419