Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2018, 07:08 AM
  • 05 2291_05 2290 _01042018_230848.mp4

Date
01/04/2018
W/O
679437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00429
PipeID
P07414
Time
11:08 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5366
Sewer Name
05 COLDEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_679437_TV05094_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 2291
Downstream MH
05 2290
Dir. of Survey
Downstream
Length Surveyed
335.5 ft.
Total Length
335.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2B00
O&M Rating
34
Overall Index
2
Overall Quick
Overall Rating
34
Pipe schematic from manhole 05 2291 to 05 2290
MH: 05 2291MH: 05 2290downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 2291196.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start274.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"314.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"334.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish335.5 ft. AMH - Downstream Manhole, Survey Ends - 05 2290

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    247.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
196.4TFA
0MWM
335.5AMH05 2290
314.7TFA
334.4DAE
274.7TFA
0MWL
247.9DAE
0AMH05 2291
234.3TFA

Properties (6)

additional_info
SC346443
custom_field_two
4
customer
LACSD
datetime
2018-01-04T23:08:42-08:00
sewer_category
Gravity
year_laid
28956