Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2018, 07:04 AM
  • 22 0269_22 1388_09012018_230520.mp4

Date
01/09/2018
W/O
679393
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16554
Time
11:04 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5409
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679393_TV22016_JAN2018
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0269
Downstream MH
22 1388
Dir. of Survey
Downstream
Length Surveyed
119.1 ft.
Total Length
119.1 ft.
Structural Index
3
Structural Quick
3D2D
Structural Rating
115
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
115
Pipe schematic from manhole 22 0269 to 22 1388
MH: 22 0269MH: 22 1388downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 02690 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.1 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK119.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish119.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK119.1 ft. AMH - Downstream Manhole, Survey Ends - 22 1388119.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK119.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0AMH22 0269
119.1MGOCONNECTION AT MH 12 O'CLOCK
119.1SAP
60.2TFC
88.2TFC
119.1MGOCONNECTION AT MH 3 O'CLOCK
2.1SSS
10.5TFC
112.4TFC
119.1AMH22 1388
119.1MGOCONNECTION AT MH 9 O'CLOCK
2.1SAP
119.1SSS
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0MWL
35.2TFC

Properties (5)

additional_info
SC346783
custom_field_two
2
customer
LACSD
datetime
2018-01-09T23:04:58-08:00
sewer_category
Gravity