Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2018, 10:34 AM
  • 22 0253_22 0252_10012018_023430.mp4

Date
01/10/2018
W/O
679393
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16535
Time
2:34 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5409
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679393_TV22016_JAN2018
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0253
Downstream MH
22 0252
Dir. of Survey
Downstream
Length Surveyed
363.6 ft.
Total Length
363.6 ft.
Structural Index
2
Structural Quick
322I
Structural Rating
110
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
111
Pipe schematic from manhole 22 0253 to 22 0252
MH: 22 0253MH: 22 0252downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02532.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.7 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES85.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start134.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.8 ft. RFL - Roots Fine Lateral, at 10 o'clock283.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"358 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish363.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK363.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish363.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0252

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    7.7 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
283.9TFC
85.4TFC
234.8TF
234.8RFL
363.6MGOCONNECTION AT MH 3 O'CLOCK
0MWL
286.8TFC
2.1MGOMAG COAT
143.4TF
0MGOCONNECTION AT MH 9 O'CLOCK
350.6TF
363.6SAP
182.9TFC
134.5TFC
358SSS
0MGOCONNECTION AT MH 3 O'CLOCK
0MWM
363.6AMH22 0252
2.1SAP
7.7CM
100SSS
0AMH22 0253

Properties (5)

additional_info
SC346783
custom_field_two
2
customer
LACSD
datetime
2018-01-10T02:34:08-08:00
sewer_category