Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2018, 07:42 AM
  • 22 0265_22 0264_09012018_234406.mp4

Date
01/09/2018
W/O
679393
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16548
Time
11:42 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5409
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679393_TV22016_JAN2018
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0265
Downstream MH
22 0264
Dir. of Survey
Downstream
Length Surveyed
440.3 ft.
Total Length
440.3 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
264
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
264
Pipe schematic from manhole 22 0265 to 22 0264
MH: 22 0265MH: 22 0264downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02650 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. MGO - General Observation - mag coat2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"46.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"103 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"140 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"157.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.4 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"259.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"315.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"360.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"381.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"410.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"440.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish440.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0264440.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK440.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
440.3SAP
140TFC
308.1TFC
103TFC
315.4TF
205.4TFC
0MWL
248.4TS
381.5TFC
137.7TFA
440.3AMH22 0264
46.3TFC
213.8TFC
2.1MGOmag coat
360.6TF
0AMH22 0265
2.1SAP
157.2TFC
107.8TF
440.3MGOCONNECTION AT MH 9 O'CLOCK
259.4TFC
410.2TFC
0MWM
5.8TF
54.9TFC
440.3MGOCONNECTION AT MH 3 O'CLOCK

Properties (5)

additional_info
SC346783
custom_field_two
3
customer
LACSD
datetime
2018-01-09T23:42:00-08:00
sewer_category
Gravity