Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2018, 07:20 AM
  • 22 1388_22 0268_09012018_232012.mp4

Date
01/09/2018
W/O
679393
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16553
Time
11:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5409
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679393_TV22016_JAN2018
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1388
Downstream MH
22 0268
Dir. of Survey
Downstream
Length Surveyed
43.1 ft.
Total Length
43.1 ft.
Structural Index
3
Structural Quick
3828
Structural Rating
40
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole 22 1388 to 22 0268
MH: 22 1388MH: 22 0268downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 13880 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish43.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish43.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK43.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0268

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
0.1MGOCONNECTION AT MH 6 O'CLOCK
43.1SSS
43.1SAP
2.1SSS
43.1MGOCONNECTION AT MH 9 O'CLOCK
2.2SAP
0AMH22 1388
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0.1MGOCONNECTION AT MH 3 O'CLOCK
43.1AMH22 0268

Properties (5)

additional_info
SC346783
custom_field_two
2
customer
LACSD
datetime
2018-01-09T23:20:00-08:00
sewer_category
Gravity