Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2018, 07:04 AM
  • 22 0249_22 0248 _10012018_230431.mp4

Date
01/10/2018
W/O
679393
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16531
Time
11:04 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5411
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679393_TV22016_JAN2018
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0249
Downstream MH
22 0248
Dir. of Survey
Downstream
Length Surveyed
295.1 ft.
Total Length
295.2 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
292
O&M Index
2
O&M Quick
3112
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
297
Pipe schematic from manhole 22 0249 to 22 0248
MH: 22 0249MH: 22 0248downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 02490 ft. MWL - Water Level, 20 %of cross sectional area2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"82.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.3 ft. RFJ - Roots Fine Joint, from 09 to 01 o'clock, within 8 inches of joint: YES161 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"164 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. RFJ - Roots Fine Joint, from 09 to 02 o'clock, within 8 inches of joint: YES215.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0248

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 01 o'clock, within 8 inches of joint: YES

    152.3 ft. - Roots Fine Joint, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 02 o'clock, within 8 inches of joint: YES

    173.4 ft. - Roots Fine Joint, from 09 to 02 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
14.7TFC
0MWM
295.2SSS
215.8TFC
0MGOCONNECTION AT MH 3 O'CLOCK
2.3SAP
115.4TFC
164TFC
261.8TF
69.8TFC
152.3RFJ
295.2AMH22 0248
161TF
270.9TFC
173.4RFJ
2.3SSS
292.8SAP
0AMH22 0249
23.9TFC
82.1TF
0MWL