Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2018, 10:23 AM
  • 22 0254_22 0253_10012018_022316.mp4

Date
01/10/2018
W/O
679393
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16536
Time
2:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5409
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679393_TV22016_JAN2018
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0254
Downstream MH
22 0253
Dir. of Survey
Downstream
Length Surveyed
276 ft.
Total Length
276 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 22 0254 to 22 0253
MH: 22 0254MH: 22 0253downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02540 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.7 ft. MGO - General Observation - MAG COAT4.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"7.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"157.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"208.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish276 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK276 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK276 ft. AMH - Downstream Manhole, Survey Ends - 22 0253

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
276MGOCONNECTION AT MH 3 O'CLOCK
4.3TF
77.3TF
40.7TFC
0MWM
80.8TFC
2.6SAP
0AMH22 0254
2.7MGOMAG COAT
157.2TFC
7.5TFC
0MWL
205TF
276MGOCONNECTION AT MH 9 O'CLOCK
153.3TF
0.1MGOCONNECTION AT MH 9 O'CLOCK
275.8SAP
208.7TFC
276AMH22 0253

Properties (5)

additional_info
SC346783
custom_field_two
3
customer
LACSD
datetime
2018-01-10T02:23:03-08:00
sewer_category
Gravity