Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2018, 12:14 PM
  • Section#9_01 0959_01 0958__1312018__G6941.mp4

Date
01/31/2018
W/O
0686794
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00228
PipeID
P01796
Time
4:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6941
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20180127MDM_WRIGHT_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
01 0959
Downstream MH
01 0958
Dir. of Survey
Downstream
Length Surveyed
299.2 ft.
Total Length
299.2 ft.
Structural Index
3
Structural Quick
3D23
Structural Rating
87
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
87
Pipe schematic from manhole 01 0959 to 01 0958
MH: 01 0959MH: 01 0958downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM30.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE68.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H96.7 ft. MGP - General Photograph - 24" VCP137.7 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H137.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE145.2 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT150.4 ft. MGO - General Observation - 12:00 LONG SLIGHT FRACTURE170.2 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SL185.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT204 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H219 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT234.9 ft. MGO - General Observation - 12:00 LONG SLIGHT FRACTURE252.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT-JOINT TO JOINT LONGER285.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish299.2 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (6)

  • General Photograph - 24" VCP

    96.7 ft. - General Photograph - 24" VCP

  • Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

    145.2 ft. - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

  • General Observation - 12:00 LONG SLIGHT FRACTURE

    150.4 ft. - General Observation - 12:00 LONG SLIGHT FRACTURE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    219 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Observation - 12:00 LONG SLIGHT FRACTURE

    234.9 ft. - General Observation - 12:00 LONG SLIGHT FRACTURE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT-JOINT TO JOINT LONGER

    252.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT-JOINT TO JOINT LONGER

Observations (18)

DistanceCodeObservation
68.7FLH
299.2AMH4:45AM
252.8FLSLIGHT-JOINT TO JOINT LONGER
145.2FCSLIGHT
96.7MGP24" VCP
204FLH
170.2FCSL
150.4MGO12:00 LONG SLIGHT FRACTURE
137.7FCH
234.9MGO12:00 LONG SLIGHT FRACTURE
137.7FLHAIRLINE
285.6FL
30.6FLHAIRLINE
185.5FLSLIGHT
219FLSLIGHT
0MWL
0MWM
0AMH4:15AM

Properties (4)

custom_field_three
SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime