Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2018, 09:30 AM
  • Section#7_01 0946_01 0945__1302018__G6940.mp4

Date
01/30/2018
W/O
0686794
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00228
PipeID
P01783
Time
1:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6940
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20180127MDM_WRIGHT_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
01 0946
Downstream MH
01 0945
Dir. of Survey
Downstream
Length Surveyed
290.9 ft.
Total Length
290.9 ft.
Structural Index
2
Structural Quick
3X2Y
Structural Rating
631
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
631
Pipe schematic from manhole 01 0946 to 01 0945
MH: 01 0946MH: 01 0945downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 STUB0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:10AM4.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT7.7 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE9.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H9.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL12.6 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL15.4 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL15.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL17.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H17.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL17.8 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL22.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL22.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL25.2 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL28.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS28.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS28.2 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL28.2 ft. MGO - General Observation - 24" VCP28.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS28.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL28.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS106 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H109.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H270.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H290.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% HAIRLINE AT JOINTS290.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS290.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE AT JOINTS290.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% SLIGHT AT JOINTS290.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H290.9 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (4)

  • Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL

    28.2 ft. - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL

  • General Observation - 24" VCP

    28.2 ft. - General Observation - 24" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    106 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    270.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

Observations (34)

DistanceCodeObservation
28.2FCHAIRLINE AT JOINTS
12.6FCSL
290.6FL10% HAIRLINE AT JOINTS
4.6FLSLIGHT
0MWM
270.3FLH
28.2FLHAIRLINE AT JOINTS
28.2FCSL
15.4FCSL
28.2MGO24" VCP
17.8FLH
290.6FL10% SLIGHT AT JOINTS
106FLH
9.8FLH
7.7FCHAIRLINE
290.9AMH5:40AM
9.8FCSL
25.2FCSL
0MGOMH CONN 9:00 STUB
290.6FC50% HAIRLINE AT JOINTS
0MGOMH CONN 3:00 ACTIVE
28.2FCSLIGHT AT JOINTS
0MWL
28.2FCSL
290.6FC70% SLIGHT AT JOINTS
290.6FLH
22.7FCSL
15.4FCSL
17.8FCSL
28.2FLSLIGHT AT JOINTS
109.8FLH
0AMH5:10AM
17.8FCSL
22.7FCSL

Properties (4)

custom_field_three
LONG HAIRLINE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2018-01-30T01:30:09-08:00