- Date
- 01/30/2018
- W/O
- 0686794
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00228
- PipeID
- P01787
- Time
- 1:15 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6936
- Sewer Name
- 01 WRIGHT ROAD TRUNK
- City
- SOUTH GATE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 08
- Purpose
- Capital Improvement Program Assesment
- Project
- 20180127MDM_WRIGHT_ROAD_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 01 0950
- Downstream MH
- 01 0949
- Dir. of Survey
- Downstream
- Length Surveyed
- 287.8 ft.
- Total Length
- 287.8 ft.
- Structural Index
- 3
- Structural Quick
- 413a
- Structural Rating
- 770
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 770
Pipe schematic from manhole 01 0950 to 01 0949 Observation photos (5)

4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

28.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT

90.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

213.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

244 ft. - General Observation - SLIGHT FRACTURE