Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2018, 01:01 PM
  • Section#2_01 0951_01 0950__1292018__G6936.mp4

Date
01/29/2018
W/O
0686794
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00228
PipeID
P01788
Time
5:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6936
Sewer Name
01 WRIGHT ROAD TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20180127MDM_WRIGHT_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
01 0951
Downstream MH
01 0950
Dir. of Survey
Downstream
Length Surveyed
289.8 ft.
Total Length
289.8 ft.
Structural Index
3
Structural Quick
543]
Structural Rating
714
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
714
Pipe schematic from manhole 01 0951 to 01 0950
MH: 01 0951MH: 01 0950downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:20AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. FL - Fracture Longitudinal, at 08 TO 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS2 ft. FL - Fracture Longitudinal, at 08 TO 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS10.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT10.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT16.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H17.9 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H17.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H23.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H36.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H41.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H41.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H44.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H51.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL56.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL72.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT72.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H124.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL207.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL258.9 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE259 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE273 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SLIGHT FRACTURE289.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE AT JOINTS289.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT289.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% SLIGHT AT JOINTS289.2 ft. FL - Fracture Longitudinal, at 08 TO 04 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS289.2 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 10% HAIRLINE AT JOINTS289.8 ft. AMH - Downstream Manhole, Survey Ends - 6:10AM

Observation photos (4)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    72.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    207.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE

    258.9 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE

    259 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE

Observations (32)

DistanceCodeObservation
207.4FLSL
2FLHAIRLINE AT JOINTS
72.7FLSLIGHT
44.1FCH
289.2FC50% HAIRLINE AT JOINTS
17.9FCH
10.7FCSLIGHT
289.2FLSLIGHT
259BSLIGHT FRACTURE
289.8AMH6:10AM
0AMH5:20AM
2FCHAIRLINE AT JOINTS
16.2FLH
10.7FCSLIGHT
258.9BSLIGHT FRACTURE
273BSLIGHT FRACTURE
23.5FLH
2FLSLIGHT AT JOINTS
72.7FLH
56.8FCSL
2FCSLIGHT AT JOINTS
0MWL
17.9FLH
289.2FC50% SLIGHT AT JOINTS
51.4FCSL
0MWM
41.6FCH
289.2FL10% SLIGHT AT JOINTS
124.6FLSL
41.6FCH
36.8FLH
289.2FL10% HAIRLINE AT JOINTS

Properties (4)

custom_field_three
BROKEN PIPE SLIGHT FRACTURE
custom_field_two
2
customer
LACSD
datetime
2018-01-29T05:01:19-08:00