Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2017, 07:22 AM
  • 08 0033_08 0032 _28122017_233344.mp4

Date
12/28/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00035
Time
11:22 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5298
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0032
Downstream MH
08 0033
Dir. of Survey
Upstream
Length Surveyed
297.2 ft.
Total Length
297.2 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
166
Pipe schematic from manhole 08 0032 to 08 0033
MH: 08 0032MH: 08 0033upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00331.2 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK4.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish36.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"49 ft. RFJ - Roots Fine Joint, from 09 to 02 o'clock, within 8 inches of joint: YES88.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"138 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"190 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"237.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"290.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"295.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start297.2 ft. AMH - Downstream Manhole, Survey Begins - 08 0032297.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK297.2 ft. MWL - Water Level, 15 %of cross sectional area297.2 ft. MWM - Water Mark, 20 %of cross sectional area297.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0AMH08 0032
2CM
6.7TFC
248.2RFJ
0MGOCONNECTION AT MH 3 O'CLOCK
107.2TFC
296MGOSPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK
159.2TFA
208.9TFC
0MWL
260.4TFC
0MWM
297.2AMH08 0033
292.9CM
0MGOCONNECTION AT MH 9 O'CLOCK
59.6TFC

Properties (5)

additional_info
SC346772
custom_field_two
3
customer
LACSD
datetime
2017-12-28T23:22:38-08:00
sewer_category
Gravity