Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2018, 06:27 AM
  • 22 0299_22 1351 _11012018_222748.mp4

Date
01/11/2018
W/O
679291
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00794
PipeID
P16586
Time
10:27 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5412
Sewer Name
22 CAMERON TRUNK, SECTION 4
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_679261_TV22144_JAN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0299
Downstream MH
22 1351
Dir. of Survey
Downstream
Length Surveyed
307.5 ft.
Total Length
307.5 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
165
O&M Index
1
O&M Quick
1500
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
170
Pipe schematic from manhole 22 0299 to 22 1351
MH: 22 0299MH: 22 1351downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 02990 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. MMC - Material Change, Vitrified clay pipe12.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"17.8 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES23.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"29 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES37.2 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES49.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start58.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"162.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"212.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.8 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES227.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"245 ft. RFJ - Roots Fine Joint, at 07 o'clock, within 8 inches of joint: YES262.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267 ft. RFJ - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YES277.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES302.7 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES302.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES302.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.5 ft. AMH - Downstream Manhole, Survey Ends - 22 1351307.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (7)

  • Material Change, Vitrified clay pipe

    2.1 ft. - Material Change, Vitrified clay pipe

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    17.8 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    29 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    37.2 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    49.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YES

    267 ft. - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    302.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
49.6CM
262.8TFC
2.1MMC
58.9TFC
23.5TFC
267RFJ
302.7RFJ
227.5TFC
302.7FM
307.5AMH22 1351
245RFJ
17.8CM
0AMH22 0299
29CL
302.7CM
307.5MGOCONNECTION AT MH 3 O'CLOCK
173.7TFC
212.7TFC
123.9TFC
285.8RFJ
0MWL
217.8RFJ
277.7TFC
162.9TFC
109TFC
37.2CM
73.3TFC
12.7TFC
0MWM

Properties (4)

additional_info
SC346786
custom_field_two
3
customer
LACSD
datetime