Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 09:03 AM
  • 21 1072_21 1071_1252018_023816.mp4

Date
01/25/2018
W/O
0686419
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00769
PipeID
P16197
Time
1:03 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0730
Sewer Name
21 GAREY AVENUE TRUNK
City
LA VERN
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
03
Purpose
Maintenance Related
Project
20180125MDM_GAREY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
21 1072
Downstream MH
21 1071
Dir. of Survey
Downstream
Length Surveyed
188.8 ft.
Total Length
188.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3700
O&M Rating
21
Overall Index
3
Overall Quick
Overall Rating
21
Pipe schematic from manhole 21 1072 to 21 1071
MH: 21 1072MH: 21 1071downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE20.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped71.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active118.4 ft. RMJ - Roots Medium Joint, from 02 to 03 o'clock, 10 %, within 8 inches of joint: YESR - TAP ROOT118.9 ft. RMJ - Roots Medium Joint, from 06 to 12 o'clock, 35 %, within 8 inches of joint: YESR119.4 ft. MMC - Material Change, Fibreglass reinforced pipe126.2 ft. MMC - Material Change, Vitrified clay pipe186.5 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS188 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS188.4 ft. MGO - General Observation - DOWNSTREAM LINK PIPE TABS IN PLACE188.4 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS & METAL PIPE188.4 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT LINK PIPE TABS188.4 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - SMALL METAL PIPE IN BENNT UP TABS188.8 ft. MSA - Survey Abandoned - 20% BENT UP LINK PIPE TABS

Observation photos (9)

  • Roots Medium Joint, from 02 to 03 o'clock, 10 %, within 8 inches of joint: YESR - TAP ROOT

    118.4 ft. - Roots Medium Joint, from 02 to 03 o'clock, 10 %, within 8 inches of joint: YESR - TAP ROOT

  • Roots Medium Joint, from 06 to 12 o'clock, 35 %, within 8 inches of joint: YESR

    118.9 ft. - Roots Medium Joint, from 06 to 12 o'clock, 35 %, within 8 inches of joint: YESR

  • Material Change, Fibreglass reinforced pipe

    119.4 ft. - Material Change, Fibreglass reinforced pipe

  • Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS

    186.5 ft. - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS

  • Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS

    188 ft. - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS

  • General Observation - DOWNSTREAM LINK PIPE TABS IN PLACE

    188.4 ft. - General Observation - DOWNSTREAM LINK PIPE TABS IN PLACE

  • Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS & METAL PIPE

    188.4 ft. - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT UP LINK PIPE TABS & METAL PIPE

  • Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT LINK PIPE TABS

    188.4 ft. - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - BENT LINK PIPE TABS

  • Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - SMALL METAL PIPE IN BENNT UP TABS

    188.4 ft. - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - SMALL METAL PIPE IN BENNT UP TABS

Observations (17)

DistanceCodeObservation
0AMH12:55AM
0MWL
0MWM
188.4MGODOWNSTREAM LINK PIPE TABS IN PLACE
71.6TFActive
126.2MMC
186.5OBZBENT UP LINK PIPE TABS
188.8MSA20% BENT UP LINK PIPE TABS
188.4OBZBENT UP LINK PIPE TABS & METAL PIPE
119.4MMC
188OBZBENT UP LINK PIPE TABS
188.4OBZBENT LINK PIPE TABS
0MGOMH CONN 9:00 ACTIVE
118.9RMJ
20.2TFCCapped
118.4RMJTAP ROOT
188.4OBZSMALL METAL PIPE IN BENNT UP TABS

Properties (2)

customer
LACSD
datetime
2018-01-25T01:03:06-08:00