- Date
- 01/22/2018
- W/O
- 0683963
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00165
- PipeID
- P10546
- Time
- 2:53 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0729
- Sewer Name
- H JOINT OUTFALL H - UNIT 1F
- City
- SOUTH GATE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 08
- Purpose
- Capital Improvement Program Assesment
- Project
- 20180122MDM_JOINT_OUTFALL_H_UNIT_1F
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 42 in.
- Upstream MH
- H 0094
- Downstream MH
- H 0093
- Dir. of Survey
- Downstream
- Length Surveyed
- 304.8 ft.
- Total Length
- 304.8 ft.
- Structural Index
- 2
- Structural Quick
- 2200
- Structural Rating
- 4
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 4
Pipe schematic from manhole H 0094 to H 0093 Observation photos (5)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

135.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

135.7 ft. - General Observation - 42" RCP

199 ft. - General Observation - MAG COAT 60% START 8:00 TO 4:00

304.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE