Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2018, 09:17 AM
  • Section#7_H 0088_H 0087__1202018__G6928.mp4

Date
01/20/2018
W/O
0693963
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00165
PipeID
P10540
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6928
Sewer Name
H JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20180119MDM_JOINT_OUTFALL_H_UNIT_1F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0088
Downstream MH
H 0087
Dir. of Survey
Downstream
Length Surveyed
660.6 ft.
Total Length
660.6 ft.
Structural Index
4
Structural Quick
5j4t
Structural Rating
2785
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
2785
Pipe schematic from manhole H 0088 to H 0087
MH: H 0088MH: H 0087downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 6:15AM2 ft. MGO - General Observation - MAG COAT 80% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SAM - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG9.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG14.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR14.7 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR17.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: NO - CIRCUN REBAR27.4 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR134.1 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR246.2 ft. SRV - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR288.8 ft. SRV - Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR291.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR 1 BAR338.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR 1 BAR396 ft. SRV - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR435.7 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR573.4 ft. SRV - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR573.4 ft. SRV - Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR660 ft. SAM - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG660 ft. SRC - Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR660 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG660 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE660 ft. SAM - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG660 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR660.6 ft. AMH - Downstream Manhole, Survey Ends - 7:15AM

Observation photos (15)

  • General Observation - MAG COAT 80% START

    2 ft. - General Observation - MAG COAT 80% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    9.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    14.7 ft. - Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    14.7 ft. - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: NO - CIRCUN REBAR

    17.7 ft. - Surface Reinforcement Corroded, from 08 to 10 o'clock, within 8 inches of joint: NO - CIRCUN REBAR

  • Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    27.4 ft. - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    134.1 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    246.2 ft. - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    288.8 ft. - Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR 1 BAR

    338.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR 1 BAR

  • Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    396 ft. - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    435.7 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (28)

DistanceCodeObservation
0MWL
660SAMSEVERE AGG
0MWM
660SRCCIRCUM REBAR
573.4SRVCIRCUM REBAR
660.6AMH7:15AM
246.2SRVCIRCUM REBAR
14.7SRCCIRCUM REBAR
134.1SRVCIRCUM REBAR
9.8SAVSEVERE AGG
17.7SRCCIRCUN REBAR
2MGOMAG COAT 80% START
288.8SRVCIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
660SAVSEVERE AGG
396SRVCIRCUM REBAR
338.3SRVCIRCUM REBAR 1 BAR
27.4SRCCIRCUM REBAR
2SAMSEVERE AGG
660SSSBLISTERING PEELING CONCRETE
660SAMSEVERE AGG
660SRCCIRCUM REBAR
2SAMSEVERE AGG
435.7SRVCIRCUM REBAR
14.7SRCCIRCUM REBAR
0AMH6:15AM
573.4SRVCIRCUM REBAR
291.2SRVCIRCUM REBAR 1 BAR

Properties (4)

custom_field_three
CIRCUM REBAR CORRODED- 80% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2018-01-20T01:17:18-08:00