- Date
- 01/19/2018
- W/O
- 0693963
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00165
- PipeID
- P10559
- Time
- 3:01 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6926
- Sewer Name
- H JOINT OUTFALL H - UNIT 1F
- City
- HUNTINGTON PARK
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 07
- Purpose
- Capital Improvement Program Assesment
- Project
- 20180119MDM_JOINT_OUTFALL_H_UNIT_1F
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Upstream MH
- H 0108
- Downstream MH
- H 0107
- Dir. of Survey
- Downstream
- Length Surveyed
- 111.8 ft.
- Total Length
- 111.8 ft.
- Structural Index
- 3
- Structural Quick
- 3D2C
- Structural Rating
- 113
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 113
Pipe schematic from manhole H 0108 to H 0107 Observation photos (5)

2.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

6.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

23.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

42.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

94.6 ft. - Water Level, 50 %of cross sectional area