Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2017, 06:14 AM
  • 08 0066_08 0065 _27122017_223254.mp4

Date
12/27/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00068
Time
10:14 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5297
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0066
Downstream MH
08 0065
Dir. of Survey
Downstream
Length Surveyed
333 ft.
Total Length
333.1 ft.
Structural Index
3
Structural Quick
4C3H
Structural Rating
222
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
226
Pipe schematic from manhole 08 0066 to 08 0065
MH: 08 0066MH: 08 0065downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00660 ft. MWM - Water Mark, 15 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES52.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"105 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"155.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.5 ft. RML - Roots Medium Lateral, at 10 o'clock, 25 %, within 8 inches of joint: YES201.5 ft. RFC - Roots Fine Connection, from 08 to 10 o'clock201.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"232 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES234 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish234 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start256.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"305.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK333.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0065

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    38.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, from 08 to 10 o'clock

    201.5 ft. - Roots Fine Connection, from 08 to 10 o'clock

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    232 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    234 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
232FM
234CM
201.5RML
52.6TF
333.1MGOCONNECTION AT MH 3 O'CLOCK
38.9FM
0MWL
0AMH08 0066
201.5RFC
333.1AMH08 0065
305.3TFC
155.7TFC
3.1CM
105TFC
256.4TF
0MWM
330.7FM
201.5TF
234FM

Properties (5)

additional_info
SC346771
custom_field_two
2
customer
LACSD
datetime
2017-12-27T22:14:14-08:00
sewer_category
Gravity