Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2017, 08:35 AM
  • 08 0088_08 0087 _22122017_005224.mp4

Date
12/22/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00116
Time
12:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5291
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0088
Downstream MH
08 0087
Dir. of Survey
Downstream
Length Surveyed
431.4 ft.
Total Length
431.4 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
258
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
258
Pipe schematic from manhole 08 0088 to 08 0087
MH: 08 0088MH: 08 0087downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00880 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area3.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start130.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.8 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"230.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"332.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"381.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"431.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK431.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish431.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0087

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH08 0088
431.4MGOCONNECTION AT MH 9 O'CLOCK
3.8CM
179.8TS
130.4TFC
431.4CM
431.4AMH08 0087
381.2TFC
332.7TFC
0MWL
279.8TFC
0MWM
230.1TF

Properties (5)

additional_info
SC346769
custom_field_two
3
customer
LACSD
datetime
2017-12-22T00:35:32-08:00
sewer_category