Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2017, 06:18 AM
  • 08 0044_08 0043 _28122017_222952.mp4

Date
12/28/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00046
Time
10:18 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5298
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0043
Downstream MH
08 0044
Dir. of Survey
Upstream
Length Surveyed
309.6 ft.
Total Length
309.6 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
173
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
173
Pipe schematic from manhole 08 0043 to 08 0044
MH: 08 0043MH: 08 0044upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00440 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.6 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK17.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"120 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"299.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES307.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start309.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK309.6 ft. MWM - Water Mark, 20 %of cross sectional area309.6 ft. MWL - Water Level, 10 %of cross sectional area309.6 ft. AMH - Downstream Manhole, Survey Begins - 08 0043

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    10.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    240.8 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
240.8TB
309.6AMH08 0044
10.5CL
2CM
0MGOCONNECTION AT MH 9 O'CLOCK
142.1TF
91.2TFC
0MWM
0MWL
240.8TFC
189.6TFC
40.8TF
309.6CM
0AMH08 0043
308MGOSPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK
292TFC

Properties (5)

additional_info
SC346772
custom_field_two
3
customer
LACSD
datetime
2017-12-28T22:18:58-08:00
sewer_category
Gravity