Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 27, 2017, 08:48 AM
  • 08 0078_08 0077 _27122017_010438.mp4

Date
12/27/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00080
Time
12:48 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5296
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0077
Downstream MH
08 0078
Dir. of Survey
Upstream
Length Surveyed
361.8 ft.
Total Length
361.8 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 08 0077 to 08 0078
MH: 08 0077MH: 08 0078upstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 08 00780 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK, DEBRIS INSIDE0 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK1.8 ft. MGO - General Observation - ENCRUSTATION/SPALLING THROUGHOUT THE REACH60 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES67.7 ft. B - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES121.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"326.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"353.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start361.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK361.8 ft. MWL - Water Level, 10 %of cross sectional area361.8 ft. AMH - Downstream Manhole, Survey Begins - 08 0077361.8 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

    294.1 ft. - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
361.8CM
240TFC
35.4TFC
361.8AMH08 0078
0MWL
89.3TFC
188.3TFC
361.8MGOCONNECTION AT MH 9 O'CLOCK
140.7TFC
8.3CM
0AMH08 0077
0MWM
294.1B
361.8MGOCONNECTION AT MH 3 O'CLOCK, DEBRIS INSIDE
361.8MGOCONNECTION AT MH 12 O'CLOCK
360MGOENCRUSTATION/SPALLING THROUGHOUT THE REACH
301.8DSZ

Properties (5)

additional_info
SC346770
custom_field_two
1
customer
LACSD
datetime
2017-12-27T00:48:50-08:00
sewer_category
Gravity