Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2014, 08:43 AM
  • 22 0301_22 0300_20141229_010615.mp4

  • 22 0301_22 0300_20141229_010615.mp4

Date
12/29/2014
W/O
480716
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00794
PipeID
P16588
Time
12:43 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1994
Sewer Name
22 CAMERON TRUNK, SECTION 4
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_480716_TV22008_2014DECEMBER
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
22 0300
Downstream MH
22 0301
Dir. of Survey
Upstream
Length Surveyed
341.5 ft.
Total Length
341.5 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 22 0300 to 22 0301
MH: 22 0300MH: 22 0301upstream0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 8"0 ft. AMH - Upstream Manhole, Survey Ends - 01066.6 ft. MGO - General Observation - REPAIR IN LINE75.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES81.8 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES104.7 ft. MGO - General Observation - REPAIR IN LINE108.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"118.9 ft. MGO - General Observation - REPAIR IN LINE119.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"145.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"168.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"193.5 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES194.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"217.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"244.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"268.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"294.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"317.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"335.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"338.9 ft. MMC - Material Change, Vitrified clay pipe341.5 ft. AMH - Upstream Manhole, Survey Begins - 0044341.5 ft. MWM - Water Mark, 25 %of cross sectional area341.5 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • Material Change, Vitrified clay pipe

    2.6 ft. - Material Change, Vitrified clay pipe

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    148 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    266.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
341.5TFA
73.4TFC
173.2TFC
222.4TFC
147.3TFC
148FM
23.8TFC
334.9MGOREPAIR IN LINE
123.9TFC
259.7CM
0AMH0044
97.1TFC
47.2TFC
266.2FM
2.6MMC
232.8TFC
6TFC
341.5AMH0106
236.8MGOREPAIR IN LINE
0MWM
222.6MGOREPAIR IN LINE
0MWL
195.8TFA

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2014-12-29T00:43:09-08:00
sewer_category
GRAVITY