Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2017, 06:09 AM
  • 18 1228_18 1227 _07122017_221100.mp4

Date
12/07/2017
W/O
673978
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01143
PipeID
P25608
Time
10:09 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5267
Sewer Name
18 WORSHAM CREEK REPLACEMENT TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Routine Assessment
Project
WO_673978_TV18077_DEC2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 1228
Downstream MH
18 1227
Dir. of Survey
Downstream
Length Surveyed
371.2 ft.
Total Length
371.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole 18 1228 to 18 1227
MH: 18 1228MH: 18 1227downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 12280 ft. MWM - Water Mark, 15 %of cross sectional area37.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"47.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"50.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"97 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"237.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"344.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"346.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"346.7 ft. RFL - Roots Fine Lateral, at 10 o'clock366.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"371.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK371.2 ft. AMH - Downstream Manhole, Survey Ends - 18 1227

Observations (23)

DistanceCodeObservation
97TF
136.9TF
268.7TF
245.2TF
237.1TF
171.1TF
47.4TF
37.5TF
0MWL
50.5TF
346.7RFL
0AMH18 1228
371.2AMH18 1227
0MWM
366.5TF
86.3TF
346.5TF
344.9TF
195.2TF
325.6TF
286.2TF
84.7TF
371.1MGOCONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC346294
custom_field_two
4
customer
LACSD
datetime
2017-12-07T22:09:04-08:00
sewer_category
Gravity
year_laid
38658