29 0739_29 0738 _07122017_003050.mp4
3.1 ft. - Material Change, Concrete pipe (non-reinfored)
3.2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start
32 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES
86.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES
138.1 ft. - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES
155.6 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES
178.2 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES
192.5 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES
214.8 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES
237.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES
249.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES
261.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES
274.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES
284.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start
313 ft. - Material Change, Vitrified clay pipe
| Distance | Code | Observation |
|---|---|---|
| 284.2 | CM | — |
| 313 | MMC | — |
| 261.9 | FM | — |
| 214.8 | CM | — |
| 194 | TF | — |
| 313 | CM | — |
| 318.1 | AMH | 29 0738 |
| 165.1 | TF | — |
| 268.1 | TF | — |
| 124.3 | TF | — |
| 0 | MWM | — |
| 3.2 | SAV | — |
| 249.7 | FM | — |
| 0 | AMH | 29 0739 |
| 274.3 | FL | — |
| 313 | SAV | — |
| 177.4 | TF | — |
| 0 | MWL | — |
| 192.5 | FL | — |
| 32 | CL | — |
| 237.5 | TF | — |
| 237.2 | CL | — |
| 314.1 | TF | — |
| 3.1 | MMC | — |
| 0 | MGO | CONNECTION AT MH 3 O'CLOCK |
| 111.2 | TF | — |
| 46.7 | TF | — |
| 178.2 | CL | — |
| 155.6 | CL | — |
| 213.9 | TF | — |
| 86.5 | CL | — |
| 295.8 | TF | — |
| 64.6 | TF | — |
| 138.1 | FM | — |