Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 10:13 AM
  • 02 1287_02 1286_29112017_021721.mp4

Date
11/29/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03804
Time
2:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5053
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 1287
Downstream MH
02 1286
Dir. of Survey
Downstream
Length Surveyed
307.8 ft.
Total Length
307.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 02 1287 to 02 1286
MH: 02 1287MH: 02 1286downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12870 ft. MWL - Water Level, 10 %of cross sectional area4.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start307.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK307.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.8 ft. MGO - General Observation - CONNECTION AT MH 8 O'CLOCK307.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1286

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
307.8MGOCONNECTION AT MH 8 O'CLOCK
307.7MGOCONNECTION AT MH 9 O'CLOCK
307.8AMH02 1286
0MWM
0AMH02 1287
307.7CM
4.9CM
0MWL

Properties (4)

additional_info
SC346282
custom_field_two
3
customer
LACSD
datetime