Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2017, 07:48 AM
  • 05 0701_05 0700 _04122017_234916.mp4

Date
12/04/2017
W/O
674254
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00523
PipeID
P05933
Time
11:48 PM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4853
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #2
City
INGLEWOOD, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_674254_TV05106_DEC2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0701
Downstream MH
05 0700
Dir. of Survey
Downstream
Length Surveyed
265.3 ft.
Total Length
265.3 ft.
Structural Index
4
Structural Quick
4B33
Structural Rating
71
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
72
Pipe schematic from manhole 05 0701 to 05 0700
MH: 05 0701MH: 05 0700downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07010 ft. MWM - Water Mark, 20 %of cross sectional area10.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES12.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES14.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"18.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES27.6 ft. FM - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES30.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES36.8 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES40.1 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES42.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES45.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES48.9 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES52 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES55.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES58.3 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES64.3 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES65.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"73.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES76 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES79 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES82.3 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES85.1 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES88.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start117 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"168.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"216.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"256.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"260.5 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES263.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0700

Observation photos (21)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    10.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    12.8 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    18.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    27.6 ft. - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    30.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    36.8 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    40.1 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    42.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    45.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    48.9 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    52 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    55.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    58.3 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    64.3 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    73.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    76 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    79 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    82.3 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    85.1 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    88.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

    260.5 ft. - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
76FL
18.7FM
45.9FM
73.1FM
216.9TF
55.1CL
82.3FM
79FM
265.3AMH05 0700
0MWL
168.8TF
64.3FM
36.8CL
27.6FM
117TF
0AMH05 0701
58.3FM
65.4TF
256.3TF
30.5CL
42.8FL
40.1FM
52FM
0MWM
88.1FM
260.5RFJ
263.8FM
12.8FL
85.1FM
14.3TF
48.9FM
10.2FM

Properties (5)

additional_info
SC349680
custom_field_two
3
customer
LACSD
datetime
2017-12-04T23:48:42-08:00
sewer_category
Gravity