Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2017, 08:18 AM
  • 05 0699_05 0698 _05122017_001835.mp4

Date
12/05/2017
W/O
674254
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00523
PipeID
P05931
Time
12:18 AM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4853
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #2
City
INGLEWOOD, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_674254_TV05106_DEC2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0699
Downstream MH
05 0698
Dir. of Survey
Downstream
Length Surveyed
264.9 ft.
Total Length
264.9 ft.
Structural Index
4
Structural Quick
4734
Structural Rating
42
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
44
Pipe schematic from manhole 05 0699 to 05 0698
MH: 05 0699MH: 05 0698downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 06990 ft. MWL - Water Level, 15 %of cross sectional area14.2 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES17.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES26.5 ft. FM - Fracture Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES33.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES35.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES36.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"43.9 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES47.1 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES50.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES53.3 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES59.3 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES62.5 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES65.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start88.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"109.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES137 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"188.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"240.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"263 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish264.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0698264.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

Observation photos (13)

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    14.2 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    17.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

    26.5 ft. - Fracture Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    33.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    35.6 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    43.9 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    47.1 ft. - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    50.2 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    53.3 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    59.3 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    62.5 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    65.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    109.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
263FM
33.1CM
17.2CL
47.1FM
26.5FM
109.8DAGS
65.5FM
0MWM
36.6TFC
188.5TFC
50.2FL
62.5FM
264.9AMH05 0698
59.3FM
43.9FL
88.4TFC
240.3TFC
35.6FL
53.3FM
0AMH05 0699
137TF
0MWL
264.9MGOCONNECTION AT MH 9 O'CLOCK CAPPED
14.2FM

Properties (5)

additional_info
SC349680
custom_field_two
3
customer
LACSD
datetime
2017-12-05T00:18:15-08:00
sewer_category