Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2017, 11:36 AM
  • 18 0725_18 0724A _13112017_033803.mp4

Date
11/13/2017
W/O
635480
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P23804
Time
3:36 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5040
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_635480_TV18053_NOV2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
18 0725
Downstream MH
18 0724A
Dir. of Survey
Downstream
Length Surveyed
30.9 ft.
Total Length
30.9 ft.
Structural Index
2
Structural Quick
2500
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 18 0725 to 18 0724A
MH: 18 0725MH: 18 0724Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07254.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start30.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0724A30.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish30.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
30.9AMH18 0724A
0MWM
30.9SSS
0AMH18 0725
4.3SSS
30.9MGOCONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC346265
custom_field_two
3
customer
LACSD
datetime
2017-11-13T03:36:32-08:00