Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2017, 09:38 AM
  • 05 0698_05 0697 _05122017_013841.mp4

Date
12/05/2017
W/O
674254
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00523
PipeID
P05930
Time
1:38 AM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4853
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #2
City
INGLEWOOD, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_674254_TV05106_DEC2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0698
Downstream MH
05 0697
Dir. of Survey
Downstream
Length Surveyed
267 ft.
Total Length
267 ft.
Structural Index
4
Structural Quick
5144
Structural Rating
29
O&M Index
1
O&M Quick
1300
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
32
Pipe schematic from manhole 05 0698 to 05 0697
MH: 05 0698MH: 05 0697downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 06980 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MWM - Water Mark, 40 %of cross sectional area2.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES7.8 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES10.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES13.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES19.6 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES22.9 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES24.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"25.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start72.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"79.8 ft. RFJ - Roots Fine Joint, from 11 to 03 o'clock, within 8 inches of joint: YES113.6 ft. B - Broken, from 09 to 01 o'clock, within 8 inches of joint: YES116.7 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES122.8 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES124.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"175.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"224 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"265.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish267 ft. AMH - Downstream Manhole, Survey Ends - 05 0697

Observation photos (11)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    2.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    7.8 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    10.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    13.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    19.6 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    22.9 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    25.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 11 to 03 o'clock, within 8 inches of joint: YES

    79.8 ft. - Roots Fine Joint, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 09 to 01 o'clock, within 8 inches of joint: YES

    113.6 ft. - Broken, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

    116.7 ft. - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

    122.8 ft. - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
175.9TF
124.2TF
72.5TF
19.6FM
0MWL
79.8RFJ
13.8FM
2.1FL
0AMH05 0698
22.9CM
113.6B
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MWM
24.4TFC
224TF
267AMH05 0697
25.5FM
265.1FM
10.8CL
7.8FM
116.7RFJ
122.8RFJ

Properties (5)

additional_info
SC349680
custom_field_two
3
customer
LACSD
datetime
2017-12-05T01:38:15-08:00
sewer_category
Gravity